SubsTech     
SubsTech     

to Transformer oils (insulating oils)
to Properties of fluids

Synthetic transformer oil

(submitted by the website administration)

Synthetic transformer oil
Organic esters based fluid
Property Value in metric unit Value in US unit
Density at 60°F (15.6°C) 0.970 *10³ kg/m³ 60.6 lb/ft³
Kinematic viscosity at 68°F (20°C) 70 cSt 70 cSt
Kinematic viscosity at 212°F (100°C) 5.3 cSt 5.3 cSt
Fire point 322 ºC 612 ºF
Pour Point -60 ºC -76 ºF
Flash point 275 ºC 527 ºF
Autoignition point 438 ºC 820 ºF
Specific heat capacity 1880 J/(kg*K) 0.448 BTU/(lb*ºF)
Thermal conductivity at 20ºC (68ºF) 0.144 W/(m*K) 0.98 BTU*in/(hr*ft²*ºF)
Thermal expansion at 20ºC (68ºF) 7.5*10-4 ºCˉ¹ 4.2*10-4 in/(in* ºF)
Breakdown strength min.75 kV min.75 kV
Dielectric dissipation factor at 90ºC (194ºF) max.0.006 max.0.006
Permitivity at 20ºC (68ºF) 3.2 3.2

Related internal links

synthetic_transformer_fluid.txt · Last modified: 2023/12/14 by dmitri_kopeliovich
Promote in SubsTech       Creative Commons License Except where otherwise noted, this work is licensed under a Creative Commons Attribution-Noncommercial-Share Alike 3.0 License